Class 5 status
codes

Class 5 status codes do not generally impede the feeding of energy into the grid, but can
restrict it. A status code is displayed until it is acknowledged by pressing a key (the inverter,
however, continues to operate normally in the background).

461

Fault in the DSP data memory

The inverter is not feeding any
energy into the grid.

If the status code is displayed
all the time: notify a Fronius-
trained service engineer

463

AC polarity reversed

Check the AC polarity
If the status code is displayed
all the time: notify a Fronius-
trained service engineer

486

External NO contact is open

The inverter is not feeding any
energy into the grid.

Check external NO contact;
If this status code keeps recur-
ring, contact your system engi-
neer

487

Air inlet temperature sensor is
faulty

Notify a Fronius-trained ser-
vice engineer

488

AC measurement device is
faulty

Notify a Fronius-trained ser-
vice engineer

490
491

Internal communication error

Notify a Fronius-trained ser-
vice engineer

492

DC main switch is switched off

Switch on DC main switch

493

DC relay is faulty

The inverter is not feeding any
energy into the grid.

Notify a Fronius-trained ser-
vice engineer

494

Grounding fault on the control
board

495

The 3 V supply voltage on the
control board is faulty

496

The 5 V supply voltage on the
control board is faulty

497

The 14 V or 22 V supply volt-
age for the PWM driver is faulty

498

The 24 V supply voltage for the
power electronics is faulty

499

The 24 V supply voltage on the
control board is faulty

Code

Description

Behaviour

Remedy

Code

Description

Behaviour

Remedy

502

Insulation error on the solar
modules

Warning message is shown on
the display

If this status code keeps recur-
ring, contact your system engi-
neer

509

No energy fed into the grid in
the past 24 hours

Acknowledge status code;
Check whether all the condi-
tions for the problem-free feed-
ing of energy into the grid have
been met (e.g. are the solar
modules covered with snow?)
If the status indicator is dis-
played all the time: notify a Fro-
nius-trained service engineer

516

No communication possible
with the storage unit

If the status indicator appears
all the time: notify a Fronius-
trained service engineer