Meter calibration
Input of a correction value to ensure that the value shown on the inverter display corre-
sponds with the calibrated display on the electricity meter
DATCOM
Checking data communications, entering the inverter number, protocol settings
Status
Indicates data communication is taking place via a Fronius Solar Net or that a data com-
munications error has occurred
Inverter number
Sets the number (= address) of the inverter in a system with several solar inverters
Protocol type
Specifies the communications protocol to be used to transfer the data:
Device Info
For displaying the settings that will be of relevance to an energy supply company. The val-
ues shown will depend on the country setup or the device-specific settings of the inverter.
Setting range
k / M
Factory setting
-
Unit
%
Setting range
-5.0 - +5.0
Factory setting
0
Setting range
Status / inverter number / protocol type
Unit
-
Setting range
00 - 99 (00 = 100th inverter)
Factory setting
01
IMPORTANT! If a number of inverters are linked together in a data communications sys-
tem, assign a unique address to each one.
Unit
-
Setting range
Solar Net / Interface
Factory setting
Solar Net
Display area
General / MPP Tracker / Grid Monitoring / Voltage Limits / Fre-
quency Limits / P AC Reduction
General:
Setup
Country setup
Version
Version of country setup
Group
Group for updating the inverter software
MPP Tracker: