Technical Data
SRL 63-a
Inputs 
5 volt-free contacts from the limit switches of the valves
1 volt-free contact from a second SRL which may be mounted at the same boiler (interlock) 
1 volt-free contact from the low-level limiter
Outputs 
2 volt-free change-over contacts each for bypassing/deactivating the safety circuit
Thermal current I
th
: 4 A, switching capacity acc. to AC-15: 3A / 230V a. c.
1 volt-free change-over contact as a signalling contact for a second logic unit
Contactors must be interference-suppressed as per manufacturer's instructions (RC combination)
3 contacts for internal or external indication of status (pilot lamps)
Interval time 
Adjusted at our works within the range 2 to 336 hours, in compliance with TRD 24/72h
Standby period 
Adjusted at our works within the range 15 minutes to 2 hours, in compliance with TRD 1h
Purging time 
Set at our works to 5 minutes
Indicators and adjustors 
1 control panel at the PLC for triggering a test
3 pilot lamps for standby period / purging time, bypassing of the low-level limiter and deactivation of the
safety circuit
Mains voltage 
230V +10 / -15%, 50 - 60Hz 
Voltage of the safety circuit
230V, 50 - 60 Hz, optional 24V, 50 - 60 Hz
Power consumption 
26W
Protection 
Enclosure: IP 65 to EN 60529
Permissible ambient temperature 
Maximum 55°C
Case 
Field case for wall mounting, with clear lid
Case material: Polystyrene / polycarbonate, colour light gray
Cable entry / electrical connection 
5 cable glands, M 16, electrical connection via two terminal strips
Weight 
Approx. 3.3 kg