Basic setting, Factory setting, Start-up, operation, alarms and testing – Flowserve SRL63-A User Manual
Page 12: Srl 63-a, Interval: 24 h remaining: 2h

12
Basic Setting
Fac tory setting
Logic unit SRL 63-a
The logic unit for monitoring is delivered with the following factory settings:
■
Interval time: 24 hours
■
Standby period: 1 hour
■
Purging time: 5 minutes
■
Voltage of safety circuit: 230V AC
Start-up, Operation, Alarms and Testing
SRL 63-a
Start-up
Switch on the mains voltage.
Interval time starts running.
Remaining time is indicated.
Restarting the inter val time
Perform the purging process
(see "Operation").
Green pilot lamp "Standby"
flashes; yellow pilot lamp "By-
pass" is alight.
Purging time is running.
Low-level limiter is
bypassed.
Q1
Q2
Q3
Q4
I1 I2 I3 I4 I5 I6 I7 I8
L+ M
Interval:
24 h
Remaining:
2h
ESC
Fig. 6