Start-up, operation, alarms and testing – Flowserve SRL63-A User Manual
Page 14

14
Start-up, Operation, Alarms and Testing
– continued –
– continued –
The terminal strips of the logic unit SRL 63-a are electrically live during operation!
Because of the electrical currents which may flow, serious injuries are possible!
Before working on the terminal strips (assembly, disassembly, connecting the cables), al-
ways ensure that the unit is de-energized!
An external voltage is present at terminal strips X 1 (terminals 16 to 20) and X3 (ter-
minals 1 to 5).
Alarm
Standby period has expired
without purging process.
Red pilot lamp "Shutdown" is il-
luminated.
Safety circuit
interrupted.
Purging process not completed
in the specified purging time (5
min.).
For logic unit 1 and 2, the purg-
ing process is started simultane-
ously.
The safety circuit is only closed after completion of the purging process
(for sequence, see "Operation").
Testing the deactivation of the safety circuit
Press the button , then press
until the picture with the cursor
buttons is shown on the PLC dis-
play. Now press ESC and si-
multaneously (see picture
below).
The purging time is started.
When the purging time has end-
ed, the safety circuit is interrupt-
ed and then closed again after
5 seconds.
Press the button.
The display of Fig.6
is shown again.
Cursor picture in the PLC display
ESC + key
Dange r