Basic settings – Flowserve NRGS 11-2 User Manual
Page 16

6
The measuring range can be switch selected between ≥ 0.5 µS/cm und ≥ 0 µS/cm
by means of the code switch
4:
. Unscrew screws
E at the electrode terminal, remove cover G, Fig. 4, Fig. 5
2. Undo screws
H and remove cover plate O.
Code switch – 4 OFF
Measuring range
≥
0.5 µS/cm.
Code switch – 4 ON
Measuring range
≥
0 µS/cm.
3. Put cover plate
O in place and use screws H to fix it.
4. Replace cover
G and fasten screws E.
Basic Settings
Factory setting
The compact system is delivered with the following default factory settings:
■
Measuring range
≥
0
µ
S/cm
2
Switch selection of measuring range
Attention
■
Screwdriver for cross head (“Phillips”) screws, size
■
Screwdriver for slotted screws, size 2.5; completely insulated according to VDE 0680
■
Do not damage the electronic components when setting the code switch.
Tools