Wiring – Flowserve NRG 16-40 User Manual
Page 21

■
Wire equipment in series. Star-type wiring is not permitted!
■
Interlink screens of control cables such that electrical continuity is ensured and
connect them
once to the central earthing point (CEP).
■
In a CAN bus network the first and last equipment
must be provided with a
terminating resistor of 0
Ω. Fig. 22.
■
The CAN bus network must
not be interrupted while operating.
An interruption will result in high/low level alarm!
Tools
Attention
■
Screwdriver for cross head screws, size
■
Screwdriver for slotted screws, size .5, completely insulated according to VDE 0680
■
Open-end spanner 7 mm A. F.
Wiring
continued