Operational malfunctions, Operation – Flowserve NRG16-12 User Manual
Page 18
![background image](https://www.manualsdir.com/files/785036/content/doc018.png)
8
Operational Malfunctions
Fault-finding list for troubleshooting
Level electrode exposed – high-level alarm
Fault:
Mains voltage is not applied to level switch.
Remedy: Apply mains voltage. Wire electrode according to wiring diagram.
Fault:
The electrode rods have earth contact.
Remedy: Check and change position of installation.
Fault:
The internal insulation of the electrode rod is damaged.
Remedy: Replace level electrode.
High level reached – no function
Fault:
The electrode housing does not have earth connection to the boiler.
Remedy: Clean seating surfaces and insert metal joint ring (of stainless steel .430) 27 x 32,
form D, DIN 7603, bright-annealed.
Do
not insulate level electrode with hemp of PTFE tape.
Fault:
The vent hole in the protection tube does not exist, is obstructed or flooded.
Remedy: Check protection tube and, if necessary, provide vent hole.
Fault:
The isolating valves of the external measuring pot (optional extra) are closed.
Remedy: Open isolating valves.
If faults occur that are not listed above or cannot be corrected, please contact our Technical
Service or authorized agency in your country.
Operation
Operation in combination with controller NRS -8 in steam and pressurised hot water plants to
TRD 40, TRD 602, TRD 604, EN 2952, EN 2953 or other national regulations.
High-level alarm
Note
■
Should malfunctions occur during the commissioning procedure refer to chapter
“Operational Malfunctions” on page 8 in order to analyse and correct them.