Technical data – Flowserve NRS 1-51 User Manual
Page 8

8
NRS 1-51
Supply:
Mains voltage
4 VDC +/– 0 %, 0.3 A or 00 – 40 VAC +0/–5 %, 47 – 63 Hz, 0. A
External fuse
0.5 A (semi-delay)
Power consumption
7 VA
Inputs:
Electrical connection of level electrode
input for level electrode NRG ...-5, NRG ...-, 4-poles with screen
Sensitivity 0.5 μS/cm or 0 μS/cm (at 5 °C).
Stand-by input
volt-free input, 8-36 VDC, for monitoring the purging and bypass time.
Max. bypass time: 5 minutes.
Outputs:
Control circuit
volt-free make contacts, 4 V DC – 50 V AC, max. 6 A (resistive/inductive),
Contact material AgNi.
Delay of response: 3 seconds.
Provide inductive loads with RC combinations according to manufacturer's specification to ensure
interference suppression.
Signal output
volt-free output for instantaneous external signalling, 4 – 30 V AC/DC, max. 00 mA.
Indicators and adjustors
buttons for test and diagnosis,
red/green LEDs for indicating the operating mode and alarm.
3 red LEDs for diagnosis.
Housing
Housing material: base: polycarbonate, black; front: polycarbonate, grey.
Cross section of connection: x 4.0 mm
solid per wire or
x .5 mm
per stranded wire with sleeve to DIN 468 or
x .4 mm
per stranded wire with sleeve to DIN 468; terminal strips can be detached
Fixing of housing: Mounting clip on supporting rail TH 35, EN 6075
Electrical safety
Degree of contamination: , overvoltage category III to EN 600-0.
Protection
Housing: IP 40 to EN 6059
Terminal strip: IP 0 to EN 6059
Weight
approx. 0.5 kg
Technical Data