Emergency operation – Flowserve NRS 1-50 For TWO Electrodes User Manual
Page 23

3
Emergency operation
Emergency operation for water level limiter
If the level switch NRS -50 works with two level electrodes NRG ...-50 (water level limiter to TRD
604, EN 95-07, EN 953-06), the installation can continue operating in emergency operation
mode according to TRD 40 and EN 95 and EN 953 under constant supervision with
only 1 level
electrode, in case that one of the two installed level electrodes fails.
If only one electrode is used for operation change the settings as follows:
n
Switch off mains voltage.
n
Unscrew the right and left fixing screws
3
and remove the lower terminal strip
2
,
Fig. 6
n
Depending on which electrode shall be deactivated, set S or S of code switches
4
and
5
to ON.
n
Attach lower terminal strip and fasten fixing screws.
n
Apply mains voltage, equipment is re-started.
Attention
n
Record the beginning of emergency operation in the boiler log.
n
An installation operating in emergency mode has to be constantly supervised.
n
Immediately replace faulty level electrode.
n
Record the end of emergency operation in the boiler log.
n
When the emergency operation is over, restore original settings.
Code switch
4
Code switch
5
S
S
S
S
Level electrode activated
OFF
OFF
Level electrode deactivated
ON
ON
Level electrode activated
OFF
OFF
Level electrode deactivated
ON
ON
4
Toggle switch, white
5
Toggle switch, white
If faults occur that are not listed above or cannot be corrected, please contact our service centre or
authorized agency in your country.