Operation, alarm and test, Troubleshooting – Flowserve NRS 1-50 For TWO Electrodes User Manual
Page 20

0
Operation
Activity
Indication
Function
Level electrode(s) submerged.
Green LEDs for level
electrode / illuminated.
Output contacts are closed.
Signal outputs / open.
Alarm
Level electrode(s) exposed,
level below low water level
(LW).
Red LEDs
for level electrode / are
flashing.
De-energizing delay is running.
Signal outputs / are closed instantaneously.
Red LEDs
for level electrode /
illuminated.
Delay time has elapsed, output contacts open.
Signal outputs / are closed.
Test channel 1 and 2
During operation:
Press key or and hold it
down until the end of the test,
level switch must react as if
there was an alarm.
Red LEDs
for level electrode / are
flashing.
Alarm simulated in channel or .
De-energizing delay is running.
Signal outputs / are closed instantaneously.
Red LEDs
for level electrode /
illuminated.
Delay time has elapsed, output contacts open.
Signal outputs / are closed.
Test finished.
Operation, Alarm and Test
Indicators and adjustors
Fig. 14
Attention
Before carrying out the fault diagnosis please check:
Mains supply:
Is the level switch supplied with the mains voltage specified on the name plate?
Wiring:
Is the wiring in accordance with the wiring diagram and the relevant schematic
representation of arrangement?
Configuration: Are the code switch settings
4
and
5
correct for the number of level
electrodes used?
LED alarm /
operating mode
Level electrode 1
Test & diagnosis
button
LED alarm /
operating mode
Level electrode 2
Test & diagnosis
button
Diagnosis LED
Troubleshooting
Indication, diagnosis and remedy