Fault indication and troubleshooting – Flowserve NRS 1-50 For TWO Electrodes User Manual
Page 21

Fault Indication and Troubleshooting
– continued –
Diagnosis
Display 1 and activity
Display 2
Fault
Remedy
LED alarm and
diagnosis LED
illuminated. Press and hold
down
key 1.
Diagnosis
LED
flashing.
Malfunction in level electrode ,
malfunction in level switch,
faulty wiring,
faulty measuring voltage.
– check wiring,
– measure electrode voltages,
– clean and, if necessary, exchange
–
level electrode,
– exchange level switch.
Diagnosis
LED
flashing.
Malfunction in level electrode ,
malfunction in level switch,
faulty wiring.
Diagnosis
LED 3
flashing.
Interference voltage causing
malfunction, boiler earth without
PE
Provide screen and earthing,
connect boiler with PE.
LED alarm and
Diagnosis LED
illuminated. Press and hold
down
key 2
Diagnosis
LED
flashing.
Malfunction in level electrode ,
malfunction in level switch,
faulty wiring,
faulty measuring voltage.
– check wiring,
– measure electrode voltages,
– clean and, if necessary, exchange
–
level electrode,
– exchange level switch.
Diagnosis
LED
flashing.
Malfunction in level electrode ,
malfunction in level switch,
faulty wiring.
Diagnosis
LED 3
flashing.
Interference voltage causing
malfunction, boiler earth without
PE.
Provide screen and earthing,
connect boiler with PE.
LED alarm and
and Diagnosis LED 3
illuminated. Press and hold
down
key 1 or 2.
Diagnosis
LED
flashing.
Malfunction in processor, stand-
by fault.
Observe operating instructions for
the logic unit SRL. Replace level
switch.
Diagnosis
LED
flashing.
Internal voltage fault.
Replace level switch.
Diagnosis
LED 3
flashing.
Malfunction in relay.
Once the fault is eliminated, the level switch returns to normal operation.
After elimination of the fault switch off the mains voltage and switch it on again after approx. 5 sec.
Fault indication
Status
Diagnosis
Function
Next activity
Faulty evaluation of level
electrode , channel
Diagnosis LED and
LED alarm illuminated.
Output contacts are opened
instantaneously.
Signal output closes
instantaneously.
next:
Press
key 1.
Faulty evaluation of level
electrode , channel
Diagnosis LED and
LED alarm illuminated.
Output contacts are opened
instantaneously.
Signal output closes
instantaneously.
next:
Press
key 2.
Malfunction in level switch
detected.
Diagnosis LED 3 and
LED alarm and
illuminated.
Output contacts are opened
instantaneously.
Signal outputs and are closed
instantaneously.
next:
Press
key 1 or
key 2.
Indication, diagnosis and remedy
– continued –