Fault Indication and Troubleshooting

– continued –

Diagnosis

Display 1 and activity

Display 2

Fault

Remedy

LED alarm and

diagnosis LED

illuminated. Press and hold

down

key 1.

Diagnosis

LED

flashing.

Malfunction in level electrode ,

malfunction in level switch,

faulty wiring,

faulty measuring voltage.

– check wiring,

– measure electrode voltages,

– clean and, if necessary, exchange

level electrode,

– exchange level switch.

Diagnosis

LED

flashing.

Malfunction in level electrode ,

malfunction in level switch,

faulty wiring.

Diagnosis

LED 3

flashing.

Interference voltage causing

malfunction, boiler earth without

PE

Provide screen and earthing,

connect boiler with PE.

LED alarm and

Diagnosis LED

illuminated. Press and hold

down

key 2

Diagnosis

LED

flashing.

Malfunction in level electrode ,

malfunction in level switch,

faulty wiring,

faulty measuring voltage.

– check wiring,

– measure electrode voltages,

– clean and, if necessary, exchange

level electrode,

– exchange level switch.

Diagnosis

LED

flashing.

Malfunction in level electrode ,

malfunction in level switch,

faulty wiring.

Diagnosis

LED 3

flashing.

Interference voltage causing

malfunction, boiler earth without

PE.

Provide screen and earthing,

connect boiler with PE.

LED alarm and

and Diagnosis LED 3

illuminated. Press and hold

down

key 1 or 2.

Diagnosis

LED

flashing.

Malfunction in processor, stand-

by fault.

Observe operating instructions for

the logic unit SRL. Replace level

switch.

Diagnosis

LED

flashing.

Internal voltage fault.

Replace level switch.

Diagnosis

LED 3

flashing.

Malfunction in relay.

Once the fault is eliminated, the level switch returns to normal operation.
After elimination of the fault switch off the mains voltage and switch it on again after approx. 5 sec.

Fault indication

Status

Diagnosis

Function

Next activity

Faulty evaluation of level

electrode , channel

Diagnosis LED and

LED alarm illuminated.

Output contacts are opened

instantaneously.

Signal output closes

instantaneously.

next:

Press

key 1.

Faulty evaluation of level

electrode , channel

Diagnosis LED and

LED alarm illuminated.

Output contacts are opened

instantaneously.

Signal output closes

instantaneously.

next:

Press

key 2.

Malfunction in level switch

detected.

Diagnosis LED 3 and

LED alarm and

illuminated.

Output contacts are opened

instantaneously.

Signal outputs and are closed

instantaneously.

next:

Press

key 1 or

key 2.

Indication, diagnosis and remedy

– continued –