beautypg.com

Flowserve Modutronic 20 II Modulating Position Controlle User Manual

Page 17

background image

1

Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06

flowserve.com

3. Rotate OFF TIME Potentiometer 8 turns CW

z

.

4. This will provide a 0.04 second ON pulse and a 0.5 second OFF pulse.

NOTE:

a. Rotating the ON TIME Potentiometer CW

z

will increase the ON time.

b. Rotating the OFF TIME Potentiometer CW

z

will increase the OFF time.

c. Adjusting one control (ON or OFF TIME Potentiometer) will affect the adjustment of the other

control (ON or OFF Time Potentiometer).

NOTE:

a. Electromechanical Starters should not exceed 100 total starts per hour.

b. Solid-State Reversers should not exceed 600 total starts per hour.