Kammer control valves, 6 technical data – Flowserve 4 Series Kämmer Pneumatic and Electropneumatic Actuators User Manual
Page 20
20
Flow Control Division
Kammer Control Valves
47
48
49
49D
37
38
39
39D
IP-37
IP-38
IP-39
IP-39D
Diaphragm area
cm
2
80
200
500
2 x 500
80
200
500
2 x 500
80
200
500
2 x 500
Thrust max.
kg
160
400
1000
2000
160
400
1000
2000
160
400
1000
2000
Stroke
mm
10/20
10/20 10/20/40 10/20/40
10/20
10/20
10/20/40 10/20/40
10/20
10/20
10/20/40 10/20/40
Time at stroke10 mm
s*
0.1
0.25
0.5
1
0.5
1
2.5
5
0.5
1
2.5
5
20 mm
s*
0.2
0.5
1
2
1
2
5
10
1
2
5
10
40 mm
s*
–
–
2
4
–
–
10
20
–
–
10
20
Signal range
3 – 15 psi
3 – 15 / 3 – 9 / 9 – 15 psi
0/4 – 20, 4 – 12, 12 – 20 mA or rev.
0.2 – 1.0 bar
0.2 – 1.0 / 0.2 – 0.6 / 0.6 – 1.0 bar
–
20 – 60 kPa
20 – 100 / 20 – 60 / 60 – 100 kPa
–
Input resistance
–
–
260/170 Ohm**
Inductivity / Capacitance
–
–
negligible (
≈
0)
Spring range
see appropriate spare parts list
see appropriate spare parts list
see appropriate spare parts list
Supply pressure
20 – 60 psi
20 – 60 psi
20 – 60 psi
1.4 – 4.2 bar
1.4 – 4.2 bar
1.4 – 4.2 bar
140 – 420 kPa
140 – 420 kPa
140 – 420 kPa
Accuracy
–
±
1%
= 1%
Hysteresis
–
< 1%
= 1%
Operating sensitivity
–
–
= 0.1%
Amplification factor
–
50
50
Supply pressure influence
–
0.4% / 0.1 bar
0.4% / 0.1 bar
Air consumption at 1,4 bar
–
0.6 Nm
3
/ h
0.6 Nm
3
/ h
Electrical protection
–
–
EEx ia C T6, PTB No. Ex-93.C. 2104X
Suitable for connection to intrinsical
safe circuits with I max.
= 60 mA (T6) thru 150 mA (T4)
Housing protection
–
–
IP 54
Allowable ambient temp. – 30 to + 80
°
C (-22 to +176
°
F)
Actuator action
air-to-open / air-to-close, reversible
Installation position
optional
Air supply
dry and oil-free (instrument air)
8.6 TECHNICAL DATA
Actuator without positioner
Actuator with P/P positioner
Actuator with I/P positioner
<
<
<
<
*
Stroking time with 1.4 bar supply pressure.
** Transducer adjustable = 260 Ohm, not adjustable = 170 Ohm