beautypg.com

Kämmer, 63 mm, Range adjust- ment screw – Flowserve 4 Series Kämmer Pneumatic and Electropneumatic Actuators User Manual

Page 18: Gauge (scale 1:1) dim. "a, Positioner spring adjusting nut actuator stem, Gauge set screw, 8calibration calibrate actuator

background image

18

Flow Control Division

Kammer Control Valves

Fig. 14: Dial gauge

Adjust positioner spring with gauge

Fig. 15

KÄMMER

39D>

37/38/39
39D<
39D>

37/38/39
39D<

38-2
39D>

38-2
39
39D<

10

10
10
20

20
20

10
40

20
40
40

Type

H

Positioner spring

Adjusting nut

Actuator stem

Range adjust-
ment screw

(max. 3 turns)

Gauge

Set screw

Gauge (scale 1:1)

Dim. "A"

8

Calibration

Calibrate actuator

(actuator without adjustable positioner spring)

8.1

Range adjustment

See nameplate for signal range, supply pressure
and stroke.

8.1.1

Connect air supply to the "SUPPLY" port of the
actuator and an adjustable signal source to the

"SIGNAL" connection. Attach a dial gauge to the
actuator (see Fig 14).

8.1.2

Undo the zero adjustment locknut until it is a few
threads free of the actuator housing. Set the
signal to the low end value (e.g. 0,2 bar or 4 mA).
Adjust the dial gauge to zero.

8.1.3

Set the signal to the high end value (e.g. 1,0 bar or
20 mA).

Zero adjustment locknut

KÄMMER

39D>

37/38/39
39D<
39D>

37/38/39
39D<

38-2
39D>

38-2
39
39D<

10

10
10
20

20
20

10
40

20
40
40

Type

H

63 mm