Troubleshooting, Fault finding list, Equipment does not work – Flowserve LRGT16-1 Spector compact Conductivity Transmitter System User Manual
Page 15

Troubleshooting
 
Fault Finding List 
Equipment does not work 
Fault: 
Supply voltage failure - no function.
Remedy:
Check power supply and all electrical connections.
 
Fault: 
Electronic insert defective.
Remedy:
Replace electronic insert.
Equipment signals malfunction 
LED display: 
Red LED flashing.
Current output: 4 mA 
Fault: 
Value below 0 % setting, e. g. electrode exposed.
Remedy:
Check water level and installation.
 
LED display: 
Red LED flashing.
Current output: 0 mA 
Fault: 
Connection to measuring tube/electrode interrupted.
Remedy:
Check electrode cables (electronic insert, terminal lugs 1 - 4). 
Replace equipment if necessary. 
 
LED display: 
Green LED flashing.
Current output: 0 mA 
Fault: 
Value above 100 % setting, e. g. control range too small.
Remedy:
Adjust larger control range.
 
LED display: 
Red LED flashing.
Current output: 0 mA 
Fault: 
Connections to measuring tube/electrode short-circuited.
Remedy:
Check electrode cables (electronic insert, terminal lugs 1 - 4). 
Replace equipment if necessary. 
 
LED display: 
Red and green LEDs flash alternately.
Current output: 0 mA 
Fault: 
Temperature in terminal box exceeds 85 °C.
Remedy:
Check ambient temperature. Make sure it does not exceed 70 °C.
 
LED display: 
Red and green LEDs flash alternately.
Current output: 0.5 mA 
Fault: 
Electrical connections to resistance thermometer interrupted or 
short-circuited or thermometer defective. 
Remedy:
Check thermometer connections (electronic insert, terminal lugs 5 + 6). 
Replace equipment if necessary. 
15