- 3 -

Characteristics

Installation

Positioning options

The modular unit is mounted on a DIN rail in the electrical
cabinet.

Installing the CTs (current transformers)

• The CT wire length can be extended by up to 1.5 m (for wire type H03VV-F or H05V-K).

• CTs do not have a connection polarity.

• It is important to check that the CT assigned to phase 1 (see connection diagrams) actually

measures phase 1 (the same must be done for phases 2 and 3).

• It is possible to pass several conductors from the same phase through a single CT (maximum

interior Ø 10 mm).

Starting up

When the

TYWATT TRI is switched on, it determines the type of meter wired

to its terminals. This takes around 10 seconds:

- The red LED is on steady.
- The consumption total begins (in Wh up to 1 kWh (fig.1), then in kWh
(fig.2)), with no indication of the price period.

After 10 seconds:

- The red LED is on and steady if TYWATT TRI is operating with an
electronic meter (see § 6.5) or flashes if TYWATT TRI is operating with an
electromechanical meter,
- The current price period indicator is displayed (fig. 3).

Note: Switch on the heating. TWATT TRI’s operation can be confirmed immediately when the counting
begins (fig.1 or fig.2).

• 230 V ±10%, 50 Hz power supply
• Class II insulation
• Power consumption: 0.5 VA
• 1 off-peak hours contact input, 230 V
• 1 remote information bus input for electronic

meter

• 3 CT inputs, current measurement by external

current transformer (internal Ø: 10 mm max.)

• Rated operating current, per phase: 2 to 60 A,

Cos

ϕ

= 0.8 to 1

• Display of the dialogue with the meter
• Storage temperature: -10°C to +70°C
• Operating temperature: 0 to +40°C
• Digital display
• Modular unit: 3 modules, h = 53 mm
• Mounting on DIN rail

1

2

3

- 2 -

Contents

1) Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

p 3

2) Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

p 3

3) Starting up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

P 3

4) Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

P 4

5) How to read your consumption indicators ? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

P 6

6) Meter indicator light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

p 7

TYWATT TRI measures the number of kilowatt-hours consumed by part of a three-phase 230 V
powered electric system (heating, DHW, etc.). It can be used with electromechanical meters as well as
with three-phase electronic meters.
TYWATT TRI performs 2 types of totals:

C1 (cumulated total since first startup, non erasable)
C2 (cumulated total since last reset, erasable)

The current is measured by external measuring devices (current transformers, CT).

Consumption value

7

Meter indicator light

6

Selection of total to consult

5

Browsing key

4

Indicated total since first start up (C1)

1

Indicated total since last reset (C2)

2

Reset for total C2

3

2

1

3

4

5

6

7

SELEC.

RESET C2