beautypg.com

Ac filter board configuration - step 1 of 3, Installation .7, Ac input terminal block – DC Power Technologies FS3 - Owners Manual User Manual

Page 7: Step

background image

AC Filter Board Configuration - Step 1 of 3

AC Input
Terminal
Block

Installation .7

Configuration 1 - MP130
208-240V AC Single Phase.

Configuration 4 - MP330
480V AC Three Phase.

STEP

1

A

E

D

C

B

L1

N

Configuration 3 - MP130
208-240V AC Three Phase.

A

E

D

C

B

L1

L2

L3

Configuration 2 - MP130
208-240V AC Single Phase Split Leg.

A

E

D

C

B

L2

208-240

N

0

L1

208-240

Note: Terminal connections
to be tightened to 21 in.lbs

Note: It is common in the US that a fourth wire (neutral) be used in a triple

phase circuit. If present, it should be attached to the “E” terminal.

208-240V AC

208-240V AC

208-240V AC

480V AC

A

E

D

C

B

L1

L2

L3