20. Troubleshooting

Troubleshooting

Problem

Possible Cause

Remedy

Main Switch Alarm.

Front panel switch in

the STOP position.

Charge will start when the

switch is set to START.

Inlet Filter Alarm.

Air inlet filter blocked.

Clean the filter.

Low Mains Alarm.

AC mains supply is

low or charger modules

may be overloaded.

Check configuration of the

charger suits the application.

Non-Urgent Module

Fail Alarm.

Charger module not providing

output, there is capacity to

charge at a reduced rate.

Replace the faulty charger

module(s).

Urgent Module

Fail Alarm.

Faulty charger modules are

affecting the ability of the

charger to charge the battery.

Replace the faulty charger

module(s).

Module Fan Fail.

Faulty charger module fan.

Replace charger module.

Module Over

Temperature.

Charger module

is overheating.

Check air inlet filter is

not blocked, check the

charger is installed without

any obstructions to air

inlet and outlet.

Configuration

Error.

Charger cannot provide the

target output current.

Check the controller

configuration matches

the quantity of power

modules installed, add

charger modules if necessary.

Output Fuse.

Blown output fuse.

Check battery polarity.

Replace blown fuse.

No Output

Current.

Charger failing

to provide the

required current.

Check operator has not been

unplugging battery mid charge

cycle or the charge profile

has allowed the battery

current to fall below 0.7A.

Monitor

ADC Fail.

Faulty MPC31

controller module.

Replace the MPC35

controller module

ensuring the replacement

is correctly configured.