Warning – Continental Fireplaces CDVS600 User Manual
Page 32

32
W415-0791 / C / 04.18.12
For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient
location. Route 2 strand solid core millivolt wire from the gas appliance to the wall switch / millivolt thermostat.
The recommended maximum lead length depends on the wire size:
WIRE SIZE
MAX. LENGTH
14
gauge
100
feet
16
gauge
60
feet
18
gauge
40
feet
DIRECT VENT MODEL CDVS600:
Disconnect one of the wire leads to the on/off switch then connect the wire
leads from the optional thermostat / wall switch / remote. See "WIRING DIAGRAM" section.
NATURAL VENT MODEL CS600:
Disconnect one of the wire leads to the on/off switch then connect the
wire leads from the optional thermostat / wall switch / remote / spill switch to "B" vent adaptor. See "WIRING
DIAGRAM" section.
30.1A
Installation and servicing to be done by a qualifi ed installer.
A.
Move the appliance into position and secure.
B.
If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.
C.
Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
D.
When
fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
E.
The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner
assembly on it’s side to aid with servicing components.
F.
Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.
!
WARNING
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SPARKS OR OPEN FLAMES.
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
5.5 MOBILE HOME INSTALLATION - MODEL CDVS600
In Canada, mobile home installation may be vented horizontally or vertically. In the United States, it may only
be installed vertically. See "VERTICAL VENTING" or "HORIZONTAL AIR TERMINAL INSTALLATION" section
for installation.
For mobile home installations, the appliance must be fastened in place. It is recommended that the appliance
be secured in all installations. Use the levelling / securing kit, GDSLL-KT for this purpose.
5.6 GAS
INSTALLATION
5.7 OPTIONAL WALL SWITCH / THERMOSTAT