0 installation preparation - model cdvs600, 1 orifice replacement – Continental Fireplaces CDVS600 User Manual
Page 23

23
W415-0791 / C / 04.18.12
Example:
V
1
= 1.5 FT
V
2
= 5 FT
V
T
= V
1
+ V
2
= 1.5 + 1 + 5 = 6.5 FT
H
1
= 1 FT
H
2
= 1 FT
H
3
= 10.75 FT
H
R
= H
1
+ H
2
+ H
3
= 1 + 1 + 10.75 = 12.75 FT
H
O
= .03 (four 90° elbows + one 45° elbow - 90°)
= .03 (360° + 45° - 90°) = 6.75 FT
H
T
= H
R
+ H
O
= 12.75 + 6.75 = 19.5 FT
H
T
+ V
T
= 19.5 + 6.5 = 26 FT
Formula 1:
H
T
< 3 V
T
3 V
T
= 3 x 6.5 = 19.5 FT
19.5 = 19.5
Formula 2:
H
T
+ V
T
< 40 FT
26 < 40
Since both formulas are met, this vent configuration is acceptable.
90°
V
1
V
2
H
1
H
2
90°
90°
H
3
45°
18.2_3
REAR VENT TERMINATION:
In rear exit installations with no vertical vent run, the BTU input must
be reduced to 21,000 BTU by changing the orifi ce.
In order to access the orifi ce, the log support secured by two screws,
must be removed.
Care should be taken not to damage the gas pipe. When removing
the orifi ce, using a socket wrench, a back-up wrench must be used
on the manifold, located below the housing, to ensure that the alumi-
num tubing does not twist or kink.
4.0 INSTALLATION PREPARATION - MODEL CDVS600
4.1 ORIFICE
REPLACEMENT