1 General informations

1.12 Table describing the alarm messages appearing on the display

DISPLAYED MESSAGE

DESCRIPTION

GENERATOR BEHAVIOUR

ACTIONS

LOW BATTERY

Indicates that the battery voltage is below the mini-

mum value necessary to start the generator.

The generator does not start.

Check the efficiency of the battery before starting

the generator.

OIL CHANGE

This message appears every time the hour counter

of the machine reaches the service interval pre-set to

change the engine oil.

The generator continues to run.

Change the oil (see p.20) before restarting the

generator by holding the start button down for

longer.

NO FUEL

Indicates that you are using the fuel reserve.

The generator continues to run.

Refuel.

OIL ALERT

There is no more oil in the oil tank.

The generator stops.

Fill up (see page 11).

GENERATOR ALERT!

General alarm message; it is displayed for instance

when the check ring of the carburettor throttle (step

motor) is defective and the M110 module cannot che-

ck the motor speed

The generator stops.

SeeTroubleshooting table on page 18. If the

problem persists, address to the nearest service

centre.

OVERLOAD!

Indicates an output overload of the supplied sy-

stems.

The inverter stops and voltage is no longer

supplied, but the engine continues to run for a

correct cooling of the internal parts.

Reduce the connected load, wait a few minutes

to cool down the generator. Stop the engine by

pressing the main switch button. Then restart

the generator.

SHORT CIRCUIT

Indicates an output short of the supplied systems.

The inverter stops and voltage is no longer

supplied, but the engine continues to run for a

correct cooling of the internal parts.

Check all the connected systems, wait a few

minutes to cool down the generator. Stop the

engine by pressing the main switch button.

OVER TEMPERATURE

This message is displayed in the event of a thermal

overload.

The inverter stops and voltage is no longer sup-

plied. The engine continues to run for a correct

cooling of the internal parts, then stops and the

message displayed is “RESTART GEN?”.

Let the generator cool down, wait a few minutes

and restart the unit.

LOW POWER ENGINE

Signals a reduction of the voltage supplied to the

inverter.

The generator stops.

Reduce the connected load and restart the

generator.

RESTART GEN?

This message appears after any stop of the ge-

nerator.

The generator stops.

Turn off and restart the generator.

GEN CAL

This message appears at the generator start-up and

indicates the calibration phase preceding any start-

up. The generator does not produce current yet.

The generator run but voltage is not supplied.

Wait a few seconds.

GEN WAIT

Message displayed between one start attempt and

the other.

The generator not run.

Wait until the message goes off before attemp-

ting a new start.

GEN ON

Indicates that the generator is running.

GEN OFF

Indicates that the generator not run or is ready to

start

The generator not run.

Push the start button if you want to restart the

generator