Electrical data – BECKHOFF FM33xx User Manual
Page 9

Technical data
4
FM33xx
Electrical data
The following tables provide a summary of the electrical and fieldbus-
specific data related to the TC-Plug.
Technical data
(Version 1F.1 26.05.2000)
FM3312
FM3332
General technical data
Power supply
24 V
DC
, +- 20% (19,2...28,8 V)
typical operating current
90 mA (24 V)
100 mA (24 V)
max. operating current
120 mA (24 V)
130 mA (24 V)
Power supply input protection
Reverse voltage
Over voltage
min. -35V
max. 35V
Potential separation
Thermocouples / PROFIBUS
500 V
rms
Thermocouples / Supply Voltage
500 V
rms
Supply Voltage / PROFIBUS
100 V
rms
Ambient temperature
Operating temperature
0...+55°C
Storage temperature
-25...+85°C
Type of protection
plug: IP65 (PROFIBUS-Connector: IP67)
Vibration
EN 60068-2-6
10 Hz <= f <= 57 Hz: 0,075mm Amplitude
57 Hz <= f <= 150 Hz: 1,0 g
Shock
EN 60068-2-27/29
15 g, 11 ms
Vibration
conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC immunity / EMC emission
conforms to EN 61000-6-2 / EN 61000-6-4
Approvals
CE, cULus*
*)
For the compliance of the cULus requirements use 4 Amp. fuse or
class 2 power supply!
Thermocouple technical data
Number of Inputs
12
32
Type of Input
Differential Input,
mV measurement,
high impedance grounded
no electrical separation
Connection
two wire, direct connection
Wiring length
max. 10 meter
Thermocouple sensor type
type K:-100...1370°C
type J:-100...900°C
Common mode input voltage range
-8 V...+8 V
Common mode rejection
typical 90 dB (independent from conversion time)
Common mode rejection
typical 150 dB (at 50 Hz or 60 Hz Rejection)
Normal mode rejection
typical 98 dB (at 50 Hz or 60 Hz Rejection)
Resolution
0.1°C per digit
Linearization Error
+-0,1°C (voltage to temperature)