background image

PT100 4-fold temperature measurement

Beckhoff II/O System

Page 6 of 10

Version : 1.1

Date : 12 March 97

Channels are pre-selected in accordance with Select 1-4 priorities.

Select1

Select2

Select4

Significance D0, D1

0

0

0

Measurement channel 1 is

selected.

1

0

0

Measurement channel 2 is

selected.

0

1

0

Measurement channel 3 is

selected.

1

1

0

Measurement channel 4 is

selected.

0

0

1

Control channel a is selected.

1

0

1

Control channel b is selected.

Pre-selection is valid with the falling edge (1=>0) of signal "Valid" D2.3.

Control channels a and b provide a specific bit pattern at selection. This allows for monitoring
of whether or not the microprocessor is active and properly operating.

Set value for control channel a: AA55 hex
Set value for control channel b: 55AA hex

The processor may be restarted by means of the D2.7 reset key if this alternating bit pattern is
not provided.