beautypg.com

Terminal diagram, Plug connection assignment and signal description – BECKHOFF PT100 User Manual

Page 10

background image

PT100 4-fold temperature measurement

Beckhoff II/O System

Page 10 of 10

Version : 1.1

Date : 12 March 97

5. Terminal diagram

Plug connection assignment and signal description

CONNECTOR X10

Plug

Pin

Signal

Description

X10

1

+

+24V supply voltage, control logic/analog
portion

X10

2

-

Ground

X10

3

Unassigned

CONNECTOR X10

Plug

Pin

Signal

Description

X20

1

-

GND for PT100 sensor

X20

2

E1

Input, PT100 sensor pick-off

X20

3

E1

Input, PT100 sensor pick-off

X20

4

I1

Constant-current source for PT100 sensor
(1mA)

X20

5

-

GND for PT100 sensor

X20

6

E2

Input, PT100 sensor pick-off

X20

7

E2

Input, PT100 sensor pick-off

X20

8

I2

Constant-current source for PT100 sensor
(1mA)

X20

9

-

GND for PT100 sensor

X20

10

E3

Input, PT100 sensor pick-off

X20

11

E3

Input, PT100 sensor pick-off

X20

12

I3

Constant-current source for PT100 sensor
(1mA)

X20

13

-

GND for PT100 sensor

X20

14

E4

Input, PT100 sensor pick-off

X20

15

E4

Input, PT100 sensor pick-off

X20

16

I4

Constant-current source for PT100 sensor
(1mA)

Important:

A bridge has to be inserted at the input for all of the unused channels. Open
inputs are capable of affecting the values of the other channels.