background image

M2510 Analog Input

Beckhoff II/O Lightbus System

Date: 20.08.93

Version : 2.0

Page 7 of 11

4. Installation Notes

Mounting

The M2510 is connected to the fibre optic ring using fibre optic connections (Beckhoff
Z1000). The maximum length of the FO cable, leading to the neighbouring boxes, should not
be more then 600m for glass fibre or 45 meters for other fibres. These values are only valid if
for bending the cable a radius of at least 30 mm is used. If plastic fibres are used, no special
tools are needed for installation of the plugs.

The M2510 is installed at the machine or simply by installing it to a cartridge carrier
according to DIN EN 50022 or DIN EN 50035.

Configuration

Before setting the system to work the desired modes of the Analog transformers have to be
adjusted by setting certain jumpers according to the following configuration table:

Input Jx.1 Jx.2 Jx.3 Jx.4 Jx.5 Jx.6

0 to 10V

o

cl

cl

cl

o

o

burden 50 Ohm

0 to 20 mA

cl

o

cl

cl

o

o

burden 500 Ohm

0 to 20 mA

o

cl

cl

cl

o

cl

-10 V to +10 V

o

cl

o

o

cl

o

0 to 1 V

o

o

cl

cl

o

o

-1 V to +1 V

o

o

o

o

cl

o

where : cl = closed

o = open

and

x = 1,2,3,4