3. Technical Data
Analog Inputs
max. 4
Analog Specifications
Uin = -10 V to 10 V ,
(voltage input)
Iin = 0 to 20 mA (current input)
burden 50 Ohm / 500 Ohm switchable
resolution: 12 Bit
Transformation Time
10 µs
Connections
plug-in unit; +,-,signal
Data Connections
fibre optic, II/O Lightbus System
Transmission Rate
2,5 MBaud, 25 µs for 32 bit
Support Voltage
Connection
±15 V, 80 mA total load, short cirquit proof
Option: +24 V/-15 V
Supply Voltage
24 V DC (±10 %)
Input Current
0,17 A (at 24 V DC without support voltage
load)
Input Impedance
1 MOhm using unipolar voltage measuring,
2 MOhm using bipolar voltage measuring,
50 Ohm / 500 Ohm measuring the current
Cartridge
closed cartridge, can be installed to cartridge
carrier according to DIN EN 50022, 50035
Size (w*h*d)
166 * 76 * 68 mm
Weight
about 700 g
Working Temperature
0 .. +55 °C
Storage Temperature
-20 .. +70 °C