M2510 Analog Input

Beckhoff II/O Lightbus System

Page 6 of 11

Version : 2.0

Date: 20.08.93

3. Technical Data

Analog Inputs

max. 4

Analog Specifications

Uin = -10 V to 10 V ,

(voltage input)
Iin = 0 to 20 mA (current input)

burden 50 Ohm / 500 Ohm switchable
resolution: 12 Bit

Transformation Time

10 µs

Connections

plug-in unit; +,-,signal

Data Connections

fibre optic, II/O Lightbus System

Transmission Rate

2,5 MBaud, 25 µs for 32 bit

Support Voltage
Connection

±15 V, 80 mA total load, short cirquit proof
Option: +24 V/-15 V

Supply Voltage

24 V DC (±10 %)

Input Current

0,17 A (at 24 V DC without support voltage
load)

Input Impedance

1 MOhm using unipolar voltage measuring,
2 MOhm using bipolar voltage measuring,
50 Ohm / 500 Ohm measuring the current

Cartridge

closed cartridge, can be installed to cartridge
carrier according to DIN EN 50022, 50035

Size (w*h*d)

166 * 76 * 68 mm

Weight

about 700 g

Working Temperature

0 .. +55 °C

Storage Temperature

-20 .. +70 °C