beautypg.com

Technical data – BECKHOFF M1410 User Manual

Page 6

background image

M1410 Parallel Input / Output

Beckhoff II/O-System

Page 6 von 14

Version : 2.0

Date : 2.8.94

3. Technical Data

Inputs / Outputs

16, can be configured for each port;

LED shows

state of all inputs / outputs

Input Specifications

24 VDC, 10 mA, digital filter

input switching voltages

0 - 8V = LOW
15 - 24V = HIGH

input delay

0,7 ms RC network
6,8 ms input latch

Output Specifications

24 VDC, max. 500 mA, short circuit proof

Output check

watchdog system 100ms

Connections

can be connected for 16 I/O; +,-,signal

Data Connection

fibre optic II/O system

Transmission Rate

2,5 MBaud, 25 µs for 32 Bit

Supply Voltage

24 VDC (± 10%)

Input Current

0,1 A (without load and input currents)

Cartridge

closed, can be installed to cartridge carrier
according to DIN EN 50022, 50035

Size (B * W * D)

170 * 76 * 68 mm

Weight

about 700 g

Working Temperature

±0..+55 øC

Storage Temperature

-20..+70 øC