I/O, Building Automation
Application Note DK9222-0810-0040
4.
Practical example for local override: commissioning of a ventilation system
To start the following ventilation system, the individual units are operated manually.
M
HR
mixed air
heater
cooler
heat recovery
flap
fan
pump
valve
3-way valve
KM2652
3-pt. drives
KM4602
analog drives
KM2652
relay contacts
HR
M
M
M
caption
M
M
M
M
M
M
M
M
M
Fig. Local override
Depending on the performance class of the connected consumers, the manual operating terminals with relay contacts
KM2614 (230 V AC, 16 A) and KM2652 (230 V AC, 6 A) are used. The KM4602 manual operating terminal for analog set value
specification is used for controlling the analog valves. The KM2652 can be used for controlling 3-point valves based on the
following configuration:
New Automation Technology
Beckhoff
4
For application notes see disclaimer on the last page
- Bus Terminal System (19 pages)
- EP-xxxx-xxxx (19 pages)
- BK2000 (30 pages)
- LC3100 (67 pages)
- BK4000 (28 pages)
- BK3xx0 (95 pages)
- BK5000 (12 pages)
- LC5200 (32 pages)
- BK7000 (29 pages)
- BK7500 (32 pages)
- BK7300 (40 pages)
- BK8100 (26 pages)
- BC2000 (28 pages)
- BC3100 (51 pages)
- BC7300 (48 pages)
- BC8100 (36 pages)
- BC3150 (112 pages)
- KL1012 (2 pages)
- KL1114 (2 pages)
- KL1164 (1 page)
- KL1232-xxxx (4 pages)
- KL1501 (19 pages)
- KL1512 (15 pages)
- KL2521-0024 (18 pages)
- KL2512 (21 pages)
- KL2612 (4 pages)
- KL2622 (9 pages)
- KL3062 (24 pages)
- KL3064 (20 pages)
- KL4132 (19 pages)
- KL4034 (25 pages)
- KL3302 (23 pages)
- KL3351 (18 pages)
- KS3681 (43 pages)
- KL4112 (18 pages)
- KL5001 (16 pages)
- KL5051 (17 pages)
- KL5101-0012 (21 pages)
- KS5111-0000 (21 pages)
- KL5121 (19 pages)
- KL6021 (20 pages)
- KL6051 (17 pages)
- Z1000 (2 pages)
- KL6071 (12 pages)
- Z1003 (2 pages)