2 connection of motors with pre-assembled cables, 1 cables – BECKHOFF AM3100 User Manual
Page 18

8 Electrical installation
Drive Technology
18 Version:
1.4
AM3100
8.2
Connection of motors with pre-assembled cables
Beckhoff offers preassembled motor and feedback cables for safe, faster and flawless installation of the
motors. Beckhoff cables have been tested with regard to the materials, shielding and connectors used. They
ensure proper functioning and compliance with statutory regulations such as EMC, UL etc. The use of other
cables may lead to unexpected interference and invalidate the warranty.
•
Carry out the wiring in accordance with the valid standards and regulations.
•
Only use our preassembled shielded cables for the power and feedback connections.
•
Connect up the shielding according to the wiring diagrams in sections 8.2.3 Incorrectly installed shielding
inevitably leads to EMC interference.
All available cable types are listed below. Should you require additional information please contact our support.
8.2.1 Cables
Motor cable with signal line
Connecting the plug connection:
Align the two plug connector (1) and (2) such that the white marking point (3) and the area (4) line up. Push the
two plug connectors together in the direction of the arrow. Ensure that the black locking ring (5) can turn freely.
Press the two plug connectors together until the locking point is reached.
To disconnect the plug connection:
Hold the plug connector (2), turn the black locking ring (1) downwards in the direction of the arrow and hold it in
this position. Now pull the plug connector (2) apart to the left in the direction of the arrow.
Specification
4x0,75 + (2x0,5)
General data
Weight
120,0 kg / km
Min. bending radius
36 mm (fixed installation), 88 mm (dynamic)
Overall diameter
8,8 mm +/-0,4 mm
Max. velocity
300 m/min
Max. acceleration
50 m/s²
Max. no. of cycles
10 Millionen
Max. horizontal length
50 m
Max. vertical length
5 m
Max. tensile load
10 N/mm²
Operating temperature
-20 to +60° C
Standards and features
UL AWM listed
80°C - 300V
CSA AWM listed
80°C - 300V