4 diagnostics – BECKHOFF EL1904 User Manual
Page 37

Operation
EL1904
35
4.4 Diagnostics
4.4.1 Diagnostic
LEDs
The LEDs Diag 1 to Diag 4 display diagnostic information for the EL1904.
4.4.1.1
Diag 1 (green)
The Diag 1 LED indicates the state of the TwinSAFE interface.
Flashing Code
Meaning
LED illuminated continuously normal
operation:
TwinSAFE communication OK
rapid flickering, alternating with 1 flash pulse
Error in S parameter (TwinSAFE parameter)
rapid flickering, alternating with 2 flash pulses
Error in I parameter (Individual parameter)
rapid flickering, alternating with 3 flash pulses
Waiting for S and I parameter
rapid flickering, alternating with 4 flash pulses
S- and I-parameter correct:
waiting for first host message
rapid flickering, alternating with 5 flash pulses
Watchdog error
rapid flickering, alternating with 6 flash pulses
CRC error
rapid flickering, alternating with 7 flash pulses
Sequence number error
rapid flickering, alternating with 8 flash pulses
Communication error in the TwinSAFE protocol
4.4.1.2
Diag 2 (red)
The Diag 2 LED illuminates red if the terminal detects an external supply or cross-circuit. The LED
extinguishes once the error is rectified.