Page 35

Operation
EL1904
33
Parameter overview
PrmName
Meaning
Values
FSoE_Address
DIP switch address
1 to 65535
Operating Mode
Digital / standstill monitoring 1 and 2
Digital / standstill 1 and 2
Sensor test channel
1 active
The clock signal for connection Input1+ is
checked at connection Input1-.
true / false
Sensor test channel
2 active
The clock signal for connection Input2+ is
checked at connection Input2-.
true / false
Sensor test channel
3 active
The clock signal for connection Input3+ is
checked at connection Input3-.
true / false
Sensor test channel
4 active
The clock signal for connection Input4+ is
checked at connection Input4-.
true / false
Logic channel 1
and 2
Logic of channels 1 and 2
- single logic
- asynchronous repetition OSSD
(sensor test must be switched off)
- any pulse repetition OSSD
(sensor test must be switched off)
- short cut is no module fault
Logic channel 3
and 4
Logic of channels 3 and 4
- single logic
- asynchronous repetition OSSD
(sensor test must be switched off)
- any pulse repetition OSSD
(sensor test must be switched off)
- short cut is no module fault
Store Code
This parameter is required for the
TwinSAFE Restore Mode
0x0000
Project CRC
This parameter is required for the
TwinSAFE Restore Mode
0x0000