BECKHOFF EK1914 User Manual
Page 35
Operation
EK1914
33
Parameter overview
PrmName
Meaning
Values
FSoE_Address
DIP switch address
1 to 4095
Standard outputs
active
In addition the safe output can be switched off
from the standard PLC. The safe output is linked
with the standard logic signal AND.
true / false
Testing of outputs
active
Test pulses for the outputs are activated
true / false
Error acknowledge
active
True:
Bus Coupler errors lead to a reset of the
TwinSAFE connection (error code 14 (0x0E)).
This error code is shown in the diagnostic data for
the connection until the user acknowledges it via
ErrAck in the TwinSAFE group.
False (Default):
Bus Coupler errors can only be reset by switching
the power supply off and back on again.
true / false
Sensor test channel
1 active
The clock signal of the “Clock output safe input 1”
connection is tested at the “Safe input 1”
connection.
true / false
Sensor test channel
2 active
The clock signal of the “Clock output safe input 2”
connection is tested at the “Safe input 2”
connection.
true / false
Logic channel 1
and 2
Logic of channels 1 and 2
- single logic
- asynchronous repetition
OSSD (sensor test must be
switched off)
- any pulse repetition
OSSD (sensor test must be
switched off)
- short cut is no module
fault
Store Code
This parameter is required for the TwinSAFE
Restore Mode
-
Project CRC
This parameter is required for the TwinSAFE
Restore Mode
-
Identity
These parameters are used internally only.
-
Detected Modules
These parameters are used internally only.
-