Technical data
KL6001
5
Technical data
Technical data
KL6001
Data transfer channel
2 (1/1), TxD and RxD, full duplex
Data transfer rate
9600 Baud (8N1) default, (max. 19200 Baud)
Bit distortion
< 3%
Connection
Spring force terminals
RS232-cable length
max. 15 m
LOW signal voltage
-18 V ... -3 V
HIGH signal voltage
3 V ... 18 V
Power supply
via K-Bus
Electrical isolation
500 Vrms (K-Bus / signal voltage)
Data buffer
128 byte receive buffer, 16 byte transmit buffer
Bit width in the Process image
I/O: 3 x 8 bits user data, 1 x 8 bits control/status (up to 5 x 8 bits user
data possible)
Configuration
no address setting, configuration setting via the bus coupler or control
system
Current consumption from K-Bus
55 mA
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration/shock resistance
conforms to IEC 68-2-6 / IEC 68-2-27
EMC resistance Burst / ESD
conforms to EN 50082 (ESD, Burst) / EN 50081
Installation position
any
Type of protection
IP20