Technical data
KL4112
5
Technical data
Technical data
KL4112
Number of outputs
2
Power supply
24 V DC via the Power contacts
Signal voltage
0 ... 20 mA
Load
< 500
Ω
Accuracy
< ± 0.1% (of the upper range value)
Resolution
15 bits, configurable 16 bits
Conversion time
app. 3.5 ms
Electrical isolation
500 Vrms (K-Bus / signal voltage)
Current consumption from K-Bus
60 mA typ.
Bit width in the process image
O: 2 x 16 bits data (2 x 8 bits control/status optional)
Configuration
no address or configuration setting
Weight approx.
80 g
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration/shock resistance
conforms to IEC 68-2-6 / IEC 68-2-27
EMC resistance Burst / ESD
conforms to EN 50082 (ESD, Burst) / EN 50081
Installation position
any
Type of protection
IP20
Connection
RUN - LED1
+O1
Power
Contacts
Shield
RUN - LED2
+O2
+24 V
0 V
Shield
Top View
Contact Assembly
13
O1
+ +
S
14
O2
S
5
C
D
6
7
8
1
A
B
2
3
4
+ O1
+O2
+24V
0V
Shield