beautypg.com

Technical data, Run - led1 error - led1 - u, Shield - u – BECKHOFF KL3351 User Manual

Page 5: Run - led2 error - led2 shield, U =0v, U =5v

background image

Technical data

KL3351

5


Technical data





Technical data

KL3351

Number of inputs

2, for one resistor bridge

Power supply

via the K-Bus

Signal voltage U

D

-16 mV ... +16 mV, configurable

Signal voltage U

ref

-10 V ... +10 V, configurable

Internal resistance

> 200 k

(U

ref

), > 1 M

(U

D

)

Power supply U

V

5 V, 20 mA

Resolution

16 bits

Conversion time

< 250 ms. Configurable

Measuring error (total measuring range)

< ± 0.1% (of the upper range value)

Filter

50 Hz, configurable

Electrical isolation

500 Vrms (K-Bus / signal voltage )

Current consumption from K-Bus

65 mA typ.

Bit width in the process image

I: 2 x 16 bits data (2 x 8 bits control/status)

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibration/shock resistance

conforms to IEC 68-2-6 / IEC 68-2-27

EMC resistance Burst / ESD

conforms to EN 50082 (ESD, Burst) / EN 50081

Installation position

any

Type of protection

IP20


RUN - LED1

Error - LED1

- U

D

+ U

D

Shield

- U

ref

+ U

ref

RUN - LED2
Error - LED2

Shield

Top View

Contacts

Contact Assembly

The power supply Uv can be obtained from the terminal
or can be feed in external.
The terminal supplies 5 V.
The maximum input voltage Uref is limited to 10 V.

-U =0V

V

+U =5V

V

13

U

r

S

-U

r

-U

V

-U

D

+ V

U

14

U

D

S

5

C
D

6

7

8

1

A
B

2

3

4

+U

D

+Uref

+Uref

+U

D

- U

D

- Uref

- U

V

- U

V

- Uref

- U

D

+U

V

+U

V