KL3311, KL3312, KL3314 and KL3302
13
User parameters
R32: Feature register
[0x1006]
The feature register specifies the terminal's operating mode.
Feature bit
no.
Description of the operating mode
Bit 0
1
User scaling (R33, R44) active [0]
Bit 1
1
Manufacturer scaling (R19, R20)
active [1]
Bit 2
1
Watchdog timer active [1]
In the delivery state, the watchdog
timer is switched on.
Bit 3
1
Sign / amount representation [0]
Sign / amount representation is active
instead of two's-complement
representation. (-1 = 0x8001)
Bit 4
1
Siemens output format [0]
This bit is used for inserting status
information on the lowest 3 bits (see
below).
Bit 5
1
Activates filter constant in R37 [0]
Bit 6
1
Deactivates the measuring current for
broken wire detection
Bit 7
-
reserved, do not change!
Bit 8
1
Reference temperature off [0]
Bit 9
-
reserved, do not change!
Bit 10
1
Checking of the lower measuring range
limit not applicable. [0]
Bit
15,14,13,12
Element
Valid measuring range
0 0 0 0
Type: L
-25°C to 900°C
0 0 0 1
Type: K
-100°C to 1,370°C
0 0 1 0
Type: J
-100°C to 1,200°C
0 0 1 1
Type: E
-100°C to 1,000°C
0 1 0 0
Type: T
-100°C to 400°C
0 1 0 1
Type: N
-100°C to 1,300°C
0 1 1 0
Type: U
-25°C to 600°C
0 1 1 1
Type: B
600°C to 1,800°C
1 0 0 0
Type: R
0°C to 1,700°C
1 0 0 1
Type: S
0°C to 1,700°C
Output in
μV
resolution
Valid measuring range
1 1 0 1
1
μV*
1.6
μV**
±30 mV
1 1 1 0
2
μV*
3.2
μV**
±60 mV
1 1 1 1
4
μV*
6.4
μV**
±120 mV (±80 mV for KL3314)
*) no scaling active
**) only manufacturer scaling active
Examples
Bit 15 to 12: 1111, no scaling active:
The output format is as follows: 1 digit corresponds to 1/16 °C or to 4
μV
Bit 15 to 12: 1111, manufacturer scaling activated via bit 1 of the feature
register:
The output format is as follows: 1 digit corresponds to 1/10 °C or to 6.4
μV