Register

description

KL3064

13

output.
R22: Under range limit: UNRL
16 bit signed integer in Y_a Gl.1.0 [0x0000]
If the actual value drops below this limit, the corresponding status bit is set
and the minimum value is output.

R23: ADC-Hardware preset
[0x1000]
Initialization of the ADC offset register.

Application parameters

R32: Feature register:
[0x1106]
The feature register determines the operating modes of the terminal.

Feature Bit No.

Mode description

Bit 0

1

User scaling (R33, R44) active [0]

Bit 1

1

Manufacturer scaling (R19, R20) active [1]

Bit 2

1

Watchdog timer active [1]
By default, the watchdog-timer is on.

Bit 3

1

Signed amount representation [0]
The signed amount format is active instead of
the 2’s complement. (-1 = 0x8001)

Bit 4

1

Siemens output format [0]
With this bit, status flags are inserted in the 3
least significant bits (see below).

Bits 7-5

-

not used, don't change

Bit 8

1

Over range protection [1]
If values exceed or fall below the limits of the
registers OVRL (R21), UNRL (R22), the status
bits are set accordingly and the measured range
is appropriately restricted.

Bit 9

1

Limit 1 active [0]
The process data is compared against limit 1
(R35) and corresponding status bits are set.

Bit 10

1

Limit 2 active [0]
The process data is compared against limit 1
(R36) and corresponding status bits are set.

Bits 15-11

-

not used, don't change


The three least significant bits are used for status evaluation if the Siemens
output format is chosen. The process data item is mapped in bits 3-15, and
bit 15 is the sign bit. The scaling of the process data in accordance with the
Siemens-format must take place over the user scaling (R33, R34)

Measured value

Bits 3-15

Bit 2

Bit 1

Bit 0

X

ERROR

Overflow

>10 V

0

0

1

<10 V

Process
data item

0

0

0


R33: User-Offset B_w
16 bit signed integer
This register contains the offset of the user straight-line equation (1.4). The
straight-line equation is activated via R32.

R34: User scaling A_w
16 bit signed integer * 2^-8
This register contains the scaling factor of the user straight-line equation
(1.4). The straight-line equation is activated via R32.

R35: Limit 1 in Y_2
If the process data exceeds or falls below this limit, the corresponding bits