Power on selltest bus terminal test, Listlis, Stop ok error – BECKHOFF BC8000 User Manual
Page 10

Basic information
10
BC8000
The operating modes of the bus coupler
When it is first switched on the bus coupler carries out a self-test to check
the functions of its components and the communications of the K bus, and
while this is going on the red I/O LED will flash. When the self-test has
been completed successfully, the bus coupler will begin to test the
attached bus terminals (the "bus terminal test”) and read in the
configuration from which it constructs an internal structure list, which is not
accessible from outside. If an error occurs the bus coupler will enter the
operating mode "STOP”. If the start-up sequence is completed without
errors the bus coupler will enter the mode "fieldbus start”.
Start-up behaviour of the
bus coupler
The bus coupler reports the error to the master by means of the Profibus
diagnostics. Clearing the error returns the bus coupler to its normal
operating mode.
Power on selltest
Bus terminal test
Structure list
listlis
PLC start/
Communication start
Stop
OK
Error