Basic information
18
BK4000
used depending on the type of the bus terminals, i.e. analog or digital
(3xhex, 0xhex). These are the identifiers for remote bus stations from third-
party manufacturers.
If there are analog and digital terminals on one BK4000, the bus coupler
uses the analog identifier 3xhex. The following table shows an overview.
Signal type
Signal direction
HEX-Value
Digital
INPUTS
02
Digital
OUTPUTS
01
Digital
INPUTS/OUTPUTS
03
Analog
INPUTS
32
Analog
OUTPUTS
31
Analog
INPUTS/OUTPUTS
33
The length information is coded automatically from 0 to 32 words. A stan-
dard length of up to 9 words is supported by every bus master. The length
up to 32 words is only supported from firmware version 3.2 and higher.
Please pay attention to lengths greater than 10 words.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Data direction I/O, I,O
Participant-Type
Participant-Class
Messages
Data width
Depending on the configuration software for the InterBus master interfaces,
the length and the ID code are entered separately or as a value in „16-bit
hex format“.
Most configuration programs permit reading of the actual configuratioan by
the master. The following table shows the possibilities of the length code.
Length of fitted periphery
Register width in the ID code
0
0
1 Word
1 Word
2 Words
2 Words
3 Words
3 Words
4 Words
4 Words
5 Words
5 Words
6 Words
6 Words 1)
7 Words
7 Words 1)
8 Words
8 Words
9 Words
9 Words
10 Words
10 Words 1)
11 - 12 Words
12 Words 1)
13 - 14 Words
14 Words 1)
15 - 16 Words
16 Words 1)
17 - 24 Words
24 Words 1)
25 - 32 Words
32 Words 1)