Error handling and diagnostics
Error code argument
The number of pulses indicates the position of the last Bus Terminal before the fault. Passive Bus Terminals,
such as a power feed terminal, are not included in the count.
In the case of some errors, rectification does not cause the power supply to leave the blink sequence. The
power supply can only be restarted by switching its supply voltage off and on again.
5.1.3
LEDs of the power supply unit (CX21000xx4) in Ebus mode
After switching on, the power supply immediately checks the connected Bus Terminal configuration. If Kbus
terminals are detected, the errorfree bootup is signaled by the red “I/O ERR LED” going out. If the “I/O ERR”
LED blinks, an error in the area of the terminals is indicated. The error code can be determined from the
frequency and number of blinks. This permits rapid rectification of the error.
Display
LED
Meaning
Us 24 V
Power supply for the CPU module. The LED lights
green if the power supply is correct.
Up 24V
Power supply for terminal bus. The LED lights green if
the power supply is correct.
L/A
off
Ebus not connected
on
Ebus connected / no data traffic
flashing
Ebus connected / data traffic on the Ebus.
CX2020, CX2030, CX2040
41