Mounting and wiring

3.11

RS422/RS485 connections (CX20x0­N031)

The CX20x0­N030 system interface provides an RS422 or RS 485 interface, COM1 (X300). It is
implemented on a 9­pole Sub­D socket strip. If more than one interface is required the system can be
extended via the Terminal Bus (K­ or E­bus) or Bus Terminals (KL/EL6021) which provide serial interfaces.
The pin assignment is shown at the bottom of the page.

The maximum baud rate on both channels is 115 kbit. The interface parameters are set via the operating
system or from the PLC program.

COM interface (socket)

Table 7: Pin assignment of the COM interface

PIN

Signal

Type

Description

2

TxD+

Data­Out +

Transmit 422

3

RxD+

Data­In +

Receive 422

5

GND

Ground

Ground

6

VCC

VCC

+5V

7

TxD­

Data­Out ­

Transmit 422

8

RxD­

Data­In ­

Receive 422

For RS 485 pins 2 and 3 (data +) must be connected, and pins 7 and 8 (data ­).

Setting the interface parameters

The interface is parameterised as follows in the delivery condition

Table 8: RS485 without echo, end point (terminated) standard setting

Function

Status

Echo on

off

Echo off

on

Auto send on

on

Always send on

off

Auto receive on

on

Always receive on

off

Term on

on

Term on

on

CX2020, CX2030, CX2040

33

Version 1.2