beautypg.com

Definite time delay – cycles, Definite time delay – seconds – Basler Electric BE1-81O/U User Manual

Page 45

background image

9137300990 Rev N

39

5.

Slowly decrease the sensing input frequency until the Setpoint 1 Pickup indicator just lights. The
sensing input frequency should be 51.11 Hz,

±0.01 Hz.

6.

Repeat steps 4 and 5 for Frequency Selector Switch settings of 52.22, 54.44, and 58.88.

Definite Time Delay – Cycles

1.

Connect the relay as shown in Figure 28.

2.

Adjust Selector Switch S7 for setpoint 1, located on the definite time circuit board controlling setpoint
1, to obtain a time delay in cycles with a x1 multiplier (S7-1 down, S7-2 down, and S7-3 up).

3.

Adjust the front panel, Setpoint 1 controls to the following settings:

Over/Under Selector Switch: Under (U) position

Frequency Selector Switch: 55.00

Time Delay Selector Switch: 11

4.

Apply operating power to the relay.

5.

Apply 60-hertz voltage to the relay sensing input. The level of voltage must exceed the setting of the
adjustable, front-panel Undervoltage Inhibit control.

6.

Ensure that the target indicators are reset.

7.

Step the sensing input frequency down from 60 Hz to 53 Hz. The Setpoint 1 Pickup indicator lights
and the test set timer begins counting. When the time delay ends, the setpoint 1 output relay and
target trips, and the test set timer stops counting. The timer should indicate 0.208 seconds (11 cycles
x 1/53,

±1.0 cycles).

8.

Restore the sensing input frequency to 60 Hz and reset the targets.

9.

Repeat steps 7 and 8 for Time Delay Selector Switch settings of 22, 44, and 88.

10.

If desired, the above steps may be performed with Selector Switch S7 configured for a time delay
multiplier of x10 (S7-1 up and S7-2 down) or x100 (S7-1 up and S7-2 up).

Definite Time Delay – Seconds

1.

Connect the relay as shown in Figure 28.

2.

Adjust Selector Switch S7 for setpoint 1, located on the definite time circuit board controlling setpoint
1, to obtain a time delay in seconds with a x1 multiplier (S7-1 down, S7-2 down, and S7-3 down).

3.

Adjust the front panel, Setpoint 1 controls to the following settings:

Over/Under Selector Switch: Under (U) position

Frequency Selector Switch: 55.00

Time Delay Selector Switch: 25

4.

Apply operating power to the relay.

5.

Apply 60-hertz voltage to the relay sensing input. The level of voltage must exceed the setting of the
adjustable, front-panel Undervoltage Inhibit control.

6.

Ensure that the target indicators are reset.

7.

Step the sensing input frequency down from 60 Hz to 53 Hz. The Setpoint 1 Pickup indicator lights
and the test set timer begins counting. When the time delay ends, the setpoint 1 output relay and
target trips, and the test set timer stops counting. The timer should indicate 2.5 seconds,

±0.05

seconds.

8.

Restore the sensing input frequency to 60 Hz and reset the targets.

9.

Repeat steps 7 and 8 for Time Delay Selector Switch settings of 22, 44, and 88.

10.

If desired, the above steps may be performed with Selector Switch S7 configured for a time delay
multiplier of x10 (S7-1 up and S7-2 down) or x100 (S7-1 up and S7-2 up).

BE1-81O/U

Testing