Output Contacts
Resistive Ratings
120 Vac:
Make, break, and carry 7 Aac continuously
250 Vdc:
Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
500 Vdc:
Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc:
Break 0.3 A (L/R = 0.04)
Targets
Electronically latched, manually reset target indicators may be optionally selected as either internally
operated or current operated.
Current operated targets require a minimum trip circuit current of 200 milliamperes and have a continuous
rating of 3 amperes, a two-minute rating of 7 amperes, and a one-second rating of 30 amperes.
Internally operated targets should be selected if the relay has normally-closed output contacts.
Type Tests
Dielectric Strength
In accordance with ANSI/IEEE C37.90, passes one-minute dielectric tests as follows:
All Circuits to Ground:
2,121 Vdc
Input Circuits to Output Circuits:
1,500 Vac or 2,121 Vdc
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989
Fast Transient Immunity
Qualified to ANSI/IEEE C37.90.1-1989
Impulse Testing
Qualified to IEC 255-5
Radio Frequency Interference
Maintains proper operation when tested for interference in accordance with IEEE C37.90.2
Shock
Withstands 15 G in each of three mutually perpendicular planes.
Vibration
Withstands 2 G in each of three mutually perpendicular planes, swept over the range of 10 to 500 Hz for a
total of six sweeps, 15 minutes each sweep.
Physical
Temperature
Operating:
–40 to 70°C (–40 to 158°F)
Storage:
–65 to 100°C (–85 to 212°F)
Weight
Single-Phase Sensing Units:
14.3 lb (6.5 kg) maximum
Three-Phase Sensing Units:
19.2 lb (8.7 kg) maximum
Case Size
All units are supplied in an S1 case size. See Section 4, Installation for case dimensions.
1-6
BE1-87G General Information
9170800990 Rev N