beautypg.com

Tests and adjustments, Required test equipment, Operational test – Basler Electric BE1-51/27C User Manual

Page 47: Preliminary instructions

background image

9137200998 Rev E

41

Tests and Adjustments

Procedures in this section are for use in testing and adjusting a relay for the desired operation in a
protective scheme. If a relay fails an operational test, or if an adjustment discloses a faulty relay, contact
Basler Electric.

Required Test Equipment

Minimum test equipment required for relay testing and adjustment is listed below. Refer to the following
figures for test setups.

Appropriate ac or dc power source for relay operation

Appropriate ac source (50- or 60-hertz as appropriate) for voltage and current testing

Dc external power source for output relay(s) test setup and timer input

Relay test set capable of delivering 40 amperes. A higher capability is needed for instantaneous
settings above 40 amperes

Timer

One shunt resistor for providing minimum target load

Operational Test

Preliminary Instructions

Perform the following steps before going on to any testing.

Step 1. Connect the relay test setup in accordance with Figures 30 through 35, depending upon the

sensing input type for your relay (see the style chart in the General Information chapter).

(a)

Sensing Input Type L (Single-Phase Sensing). Refer to Figure 30.

Note

For relays having the above sensing, only the from panel LOW range
current sense terminal(s) should be connected for a complete check of
the relay.

Ensure that timed output terminals 1 and 10 are connected.

(b)

Sensing Input Type P (Three-Phase Sensing). Refer to Figure 31.

Note

For relays having the above sensing, only the from panel LOW range
current sense terminal(s) should be connected for a complete check of
the relay.

For all three-phase relays, the test signals must connect to both the
current and voltage terminals for the same phase.

Ensure that timed output terminals 1 and 10 are connected.

BE1-51/27C

Tests and Adjustments