beautypg.com

Manual trip, Manual trip -5, Figure 5-3. target indicator test setup – Basler Electric BE1-50/51B-235 User Manual

Page 41

background image

9252000898 Rev A

BE1-50/51B-235/-236 Testing

5-5

8. Slowly increase the voltage source to provide target current and verify that the Instantaneous target

operates at the level of current determined by the Target Operating Current Jumpers.

9. Remove the target and sensing current and reset the target.

Figure 5-3. Target Indicator Test Setup

1. Configure the relay for manual trip testing:

Manual Trip

a. Connect the test setup as shown in Figure 5-1.
b. Set circuit board switch SW3 as follows:

SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation

SW3-2 = OFF (no additional time delay for the 50-A element)

SW3-3 = ON (Westinghouse CO type characteristic curves)

SW3-4 = ON (integrating reset characteristic)

c. Set TIME DIAL to 0.0
d. Set CURVE to S.

e. Set TIME PICKUP to 1.0.
f. Set INST PICKUP (50-A) to 90.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to 20 (2.0 Aac).

2. Apply 0.9 Aac to terminals 8 and 9 (0.9 Aac provides relay operating power but is below the pickup

threshold.)

3. Connect a jumper to the Time Overcurrent Manual Trip jacks. Verify that the stop input of the test set

timer recognizes a 51 contact closure.

4. Remove the jumper and the current applied at relay terminals 8 and 9.
5. Apply 0.9 Aac to terminals 8 and 9.

WARNING!

Trip circuit voltage is present at the front panel test points. When shorting the test

points, use insulated jumpers to avoid contact with these voltages.

This manual is related to the following products: