9252000898 Rev B
BE1-50/51B-235/-236 General Information
1-5
Figure 1-3. Current Sensing Input Burden (BE1-50/51B-235)
BE1-50/51B-236 Burden
illustrates the current sensing input burden characteristic.
At 0.1 Aac:
57.0 Ω
At 1.0 Aac:
6.9 Ω
Figure 1-4. Current Sensing Input Burden (BE1-50/51B-236)
Frequency Response
A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for
pickup.
Transient Response
<10% overreach with system time constants up to 40 ms.
BE1-50/51B-230 CT Burden