Basler Electric BE1-50/51B-240 User Manual
Page 13

9252000790 Rev B
5
Target Indicators
A gravity-latched, manually-reset, current-operated target indicator is provided for the time-overcurrent
(51) trip output and the instantaneous overcurrent (50) trip output. The level of trip circuit current required
to operate each target is individually controlled by a circuit board jumper. See the Controls and Indicators
chapter for jumper locations and function assignments
Target Operate Current
Jumper Position—Pins 1 and 2: Must operate
≥ 2.25 A; must not operate < 900 mA.*
Jumper Position—Pins 2 and 3: Must operate
≥ 200 mA; must not operate < 80 mA.*
∗ See Output Contacts for the maximum acceptable levels of trip circuit currents.
Output Contacts
Output contacts are surge protected and rated as follows.
Resistive Ratings
120/240 Vac:
Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc:
Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive Ratings
120/240 Vac, 125/250 Vdc:
Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).
Terminal Assignments
51 Element:
1, 10
50 Element:
2, 10
Type Tests
Isolation:
IEEE C37.90-2005
Transient Surge:
IEEE C37.90.1-2004
Radiated Interference:
IEEE C37.90.2-2004
Electrostatic Discharge:
IEEE C37.90.3-2006
Vibration:
IEC 255-21-1
Shock and Bump:
IEC 255-21-2
Environment
Operating Temperature:
–40 to 70
°C (–40 to 158°F)
Storage Temperature:
–50 to 70
°C (–58 to 158°F)
Physical
Weight:
4.3 lb (2 kg)
BE1-50/51B-240
General Information