Table 1-1. Current Ratings and Sensing Burdens
Power
Supply
Sensing Range
Designation
Actual Sensing
Range
Maximum Rating 50 or 60 Hz
F, G, or H
†
For
Phase
For
Neutral
Current
Burden Per
Input
K ∗
1
Second Continuous
1
D
0.25 - 0.5 A
144
12.0 A
0.75 A
8.5 VA
2
E
0.5 - 1.0 A
144
12.0 A
1.5 A
8.5 VA
3
F
1.0 - 2.0 A
625
25.0 A
3 A
8.5 VA
4
G
2.0 to 4.0 A
2500
50.0 A
6 A
8.5 VA
5
H
4.0 to 8.0 A
10000
100 A
12 A
8.5 VA
6
J
8.0 - 16.0 A
40000
200 A
20 A
9.5 VA
7
K
16.0 - 32.0 A
90000
300 A
20 A
14.0 VA
O, P, R, S,
or T
2
E
0.25 - 2.0 A
10000
100 A
5 A
0.2 VA
4
G
1.0 - 8.0 A
90000
300 A
10 A
0.6 VA
6
J
4.0 - 32.0 A
90000
300 A
20 A
4.8 VA
∗
Ratings other than continuous may be calculated using the equation:
t
K
I =
where:
K =
T =
I =
the indicated value
the time in seconds
maximum current
† Power Supply types F, G, and H are no longer available.
Pickup Range
Continuously adjustable over the range defined by the style number with independent ranges and
adjustments for each phase and neutral pickup.
Pickup Accuracy
±
2% or ±40 mA of pickup setting, whichever is greater.
Dropout
Within 2% of pickup.
Timing
1.5 cycles or less from onset of overcurrent condition. (30 milliseconds at 50 Hz, 25 milliseconds at 60
Hz.)
Output Contacts
Resistive Ratings
120 Vac:
Make, break, and carry 7 Aac continuously
250 Vdc:
Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
500 Vdc:
Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc:
Break 0.3 A (L/R = 0.04)
1-4
BE1-50 General Information
9171000990 Rev F