Masonry fireplace insert installation (cont.) – Avalon Firestyles 796-1990 to 1993 User Manual
Page 38

Page 38
MASONRY FIREPLACE INSERT INSTALLATION (Cont.)
Installation Using a Positive Connection (Continued)
8.
Take a look at the figure below. Make sure all of the items listed below are completed.
Non-Combustible
Material
Remove Damper or
Wire it Open
Insulation
(Optional)
Airtight Insulated
Clean-Out
Stainless Steel
Chimney Liner System
Follow Liner
Manufacturer's
Instructions on
Installation and
Support
Optional Face Seal
Must be sealed at
the top (preferable)
or with a block-off
plate
18" Min.
996 Extended 45 Flue Shown
Here Ð Follow the clearances
for the 996 Flush Top Flue
when that model is used.
9.
To install the surround panels, follow the directions listed in the section "INSTALLING SURROUND
PANELS" .
Follow the installation instructions in reverse order for periodic inspection and cleaning.